Existing Energy Monitoring Hardware

Already have meters installed? We'll tell you if our platform can read them.

If your building already has energy and water metering, you shouldn’t have to start again because the system behind it isn’t working for you. Maybe support has gone quiet, the reporting doesn’t do what you need, or you’re unsure the provider will be around. The meters are usually already there. What’s missing is a way to get the data out and onto one interface.

What we can read

  • Energy meters: any Modbus RTU meter, whatever the brand, on the same RS485 standard we use for new builds.
  • Water and other pulse-output meters: if it has a pulse output, we can read it. LoRaWAN pulse interfaces sit at the meter and talk to a gateway by radio, so nothing gets pulled back to a panel.
  • Occupied buildings: gateways backhaul over 4G, Ethernet or Wi-Fi. There are no base-building works and no tenancy access negotiations.


A building full of mixed-vintage meters isn’t a problem. If yours use something else, send us the make and model and we’ll give you a straight answer on what’s possible.

Whose software is it?

We wrote the EMS platform ourselves. There’s no third-party licence to pass through and no second vendor in the contract chain. It’s a question worth asking any metering vendor: whose software is it, and what happens to your data when the contract ends?

Know the meter is still working

Our platform checks every sensor daily, covering battery voltage, signal strength, temperature and time since last reading. If a meter stops reporting, we flag it rather than quietly averaging over the gap.

Need to prove compliance too?

Part J9 requires meters to be interlinked and collated to a single interface. Read what NCC Part J9 asks for.

Ready when you are

Energy management is where mySmart started, with 25 years in smart buildings behind us. Send us your meter schedule or a list of what’s installed, and we’ll tell you honestly whether our platform can read it. 

Learn More

Energy Management

Energy metering, monitoring and reporting on one platform

Energy Monitoring Support

Can't get a response from your energy monitoring provider? We'll help

NCC 2025 - Energy Management

What NCC Part J9 requires for energy metering

Frequently Asked Questions

Which existing meters can you read?

Any Modbus RTU energy meter, whatever the brand, and any water or other meter with a pulse output.

Not for pulse-output meters. LoRaWAN pulse interfaces sit at the meter and talk to a gateway by radio, so nothing has to be pulled back to a panel. Gateways connect over 4G, Ethernet or Wi-Fi, so there are no base-building works and no tenancy access negotiations.

Up to 32 meters per gateway run, on a daisy-chained Modbus RS485 bus with a 750m maximum cable run and a 120Ω terminating resistor at each end. There are no stars or loops. Water loggers take up to two pulse inputs each.

The platform checks every sensor daily, covering battery voltage, signal strength, temperature and time since last reading. If a meter stops reporting, we flag it rather than averaging over the gap.

If your meters are Modbus RTU or pulse-output, yes. Send us your meter schedule or a list of what’s installed and we’ll tell you whether we can read it.